-Instructions for M/1 Holiday Detector- T&R Product Instructions M/1 Pinhole Detector M/1 Information Bulletin |
|
1. DESCRIPTION The Model M/1 Holiday
Detector is a highly sensitive device designed to locate holidays
2. EQUIPMENT The Model M/1 Holiday Detector consists of:
When current of 500 or 700 (+/- 10/%) micro amperes flows in the circuit, an audible signal is actuated. The test lead wire used in the wand handle and ground wire is capable of handling a minimum of 100 milliamps at 100 volts. If replacement or additional wire is needed, make sure it meets the following requirements:
3. RECOMMENDED & PRE-ELECTRICAL TESTING PROCEDURES The protective coatings should be dry and free of all contamination prior to electrical holiday testing. Proper curing and drying time of the protective coating must be established prior to conducting electrical holiday testing. Note: Solvents retained in the protective coating film can cause erroneous indications (false holidays) during electrical testing. The dry film thickness should not exceed 20 mils when electrical holiday testing is done with the low voltage Model M/1 Holiday Detector. Film thickness should be determined with a non-destructive dry film thickness gauge to make sure limits are not exceeded. Special Note: Ordinary tap water will generally suffice to dampen the sponge electrode, provided the protective coating thickness does not exceed 10 mils. The factory recommended
practice is to use a wetting agent at all times, regardless of coating
thickness to 20 mils. Check battery voltage. Shorting the terminals of
the holiday detector can do this. If a steady, level audible signal is
heard, the battery voltage is OK. If the audible signal starts to attenuate
while testing, REPLACE batteries. Note: An output voltage drop of over
10% also indicates weak battery.
4. HOLIDAY DETECTOR ASSEMBLY Assemble the Holiday
Detector by connecting the wire leading from the handle to one terminal
of the detector and the plain end of the ground wire to the other detector
terminal. Connect the saturated (see below) electrode by means of the metal
clamp on the end of wand handle.
5. ELECTRICAL TESTING PROCEDURES The sponge electrode should contain sufficient amount of wetting solutions to assure moisture penetration from the sponge electrodes into any defect that may be present in the protective coating. Excess wetting solution should be squeezed out of the sponge electrode. Attach ground wire directly to the bare structure (substrate) under test. On coated steel structures the ground wire must be directly connected to the bare metal. On coated concrete structures the ground wire should be connected directly to the reinforcing steel embedded in the concrete. If re-bar is not present, a ground connection to the concrete can be made by placing the bare end of the ground wire against the bare concrete surface and anchor it down with a burlap bag filled with damp sand. The ground wire can be checked quickly for proper connection by contacting the wetted sponge electrode to the bare structure and observing an audible signal, indicating correct electrical continuity of the holiday detector circuit. The rate of inspection
speed of the sponge electrode over the protective coated surface should
not exceed sixty (60) linear feet per minute. Using a double stroke of
the sponge electrode over each area assures better inspection coverage
with less likelihood of any missed areas.
6. CALIBRATION Factory calibration
on Model M/1 Holiday Detectors are set at 700 micro amperes (+/- 10)
of current flow to compete the circuit for the audible signal to indicate
a coating holiday on metal substrates. For coatings on concrete substrates,
the Model M/1 must be adjusted for current flow of 500 micro amperes (+/- 10%).
7. ADJUSTMENT OF SIGNAL SYSTEM Model M/1 Holiday
Detectors with mechanical relays, the sensitivity may be changed by adjustment
of the armature contacts. The signal sensitivity is determined by the setting
of the electronic relay. Turning the adjusting screw of the potentiometer
clockwise REDUCES the
Factory setting of the sensitivity is made by having the relay just close when 80,000 ohms is across the external terminals which is the proper setting for use on coated metal substrates. For concrete substrates the sensitivity would be adjusted with a 90,000 - ohm resistor. Model M/1 Holiday Detectors, Serial Number 10181 and higher FACTORY calibration can be verified by simply depressing push buttons on the front of the instrument. Depress BLACK button (80K); Detector should signal and LED will light if detector is in calibration. Depress RED button (90K): Detector should NOT signal and LED will NOT light if detector is in calibration. If the detector signals when RED button (90K) is depressed, the unit is not in calibration and should be FACTORY calibrated prior to use. To check for proper
calibration of the detector for use on concrete substrates simply verify
unit is properly FACTORY calibrated at 80,000 ohms and then remove the
small jumper wire inside the red cover side of the detector.
8. WARRANTY 90 Days Parts &
Labor with 24-hour turn-around on all repairs.
9. SHIPPING INSTRUCTIONS All instruments being returned for repair should be sent PREPAID to either address below: Include with shipment information the nature of the problem, purchase order, serial number and return delivery address. Immediate service is guaranteed!Tinker & Rasor
Please also read our Model M/1 Information Bulletin, by clicking here. |
|
T&R
Product Instructions M/1
Pinhole Detector
|